Distortion of PV System-transformer Excitation Current Under Low Power Production

Document Type

Conference Proceeding

Publication Date

1-1-2017

Publication Title

2017 6th International Conference on Clean Electrical Power: Renewable Energy Resources Impact, ICCEP 2017

Publisher

Institute of Electrical and Electronics Engineers Inc.

First page number:

163

Last page number:

168

Abstract

The relative amount of distortion in the current generated by a PV system under low solar irradiance is known to be quite significant. This paper analyzes such distortion on the utility-side of the interconnection transformer thus including its excitation current. An approximate method that reveals the imbalance and distortion of both the phase and line currents in a 3-legged transformer is presented. The effect of these currents on those generated by the PV system is analyzed. The analysis is illustrated through an experimental test that was conducted on a 12 kW PV system which is connected to the grid through a 3-phase, 30 kVA, Δ-Y, 208/480 V transformer, when operating under low power production. © 2017 IEEE.

Language

english

UNLV article access

Share